This is how to add or remove a device on a Ziton ZP3 panel. This includes addressable ziton smoke detectors, manual callpoints, ziton sounders, A50e ziton relays, etc. Watch the video or look at the text description below. Remember, full Ziton ZP3 training is available with fire4u.co.uk.
Zoning a device on a Ziton ZP3 panel
follow these steps to add or remove a device on a Ziton ZP3 panel:
- press the menu key
- press 3 for setup
- enter the code and press enter (default code is 2000)
- press 1 zoning
- press 2 zone edit
- press 1 zone allocation
- type in the zone number you want to add/remove device from, press enter
- type in the device address (e.g. 1020 for L1 add 20) – DO NOT PRESS ENTER YET!
- Press enter if you want to add a device onto that zone
- press F1 if you want to remove a device from the zone (do not press enter)
- press the home key to ‘save’
- reset the panel
Why do you need to zone a device onto a ZP3 panel?
If you are installing a new ziton smoke detector onto a Ziton ZP3 panel, you will need to add it to a zone. You will also need to add addressable output devices such as sounders and relays onto zones as failure to do so may mean that they will not operate with the I/O mapping.